SALIENT FEATURES

True On - Line Pure Sinewave High Frequency PWM Inverter using IGBT
High frequency PWM technology using IGBT, provides high efficiency, low noise and faster transient response.

Computer Interface

The UPS can be interfaced with the host computer through Fibre Optic Cables. This enables local as well as remote monitoring of the UPS.

Modular Construction
The UPS is engineered with complete modularity. The power electronics is in the form of draw out modules having fork connectors for power and pluggable connectors for control. Modular construction facilitates easy maintenance, low MTTR and compact size.

Onsite Upgradability

These UPS system can be upgraded onsite

Options

  • External battery rack for longer backup.
  • Interactive software for remote monitoring with most popular operating systems.
  • SNMP for remote monitoring.
  • Green Power (Upto 30KVA): Unity input power factor, Input current distortion 7%, Compatibility with almost same capacity generator.

UPS Digital Manager
An alpha-numeric display with diaphragm switches provides an automatic cycling display informing the user on the operational status, active alarms and electrical parameters of the UPS, with priority to error messages. The display is automatically updated every 2 seconds, it can also be operated manually. The display can be programmed for different languages.

Auto Retransfer
The UPS has a unique feature of transferring the load automatically back to inverter as long as inverter is healthy and the load is within the capacity of the UPS.

The feature is very helpful for starting of loads, which draw starting in-rush current more than capacity of the UPS. The UPS goes to bypass on sensing over load and comes back on inverter supply automatically once the load current is settled to normal level.

Conformance to International Standards

  • Product Testing: IEC 146
  • Safety: EN50091-1
  • EMI / RFI Suppression: EN50091-2

CapacityKVA/kW

10/8

15/12

20/16

25/20

30/24

40/32

50/35

Input

Voltage Range

400V Three Phase ± 15%

Frequency

50Hz ± 10%

Output

Voltage

400V, 3phase

Frequency

50±%0.005Hz(Free running)

Power Factor

0.8

Overload

125% for 10 min and 150% for 1 min

Steady State Voltage Regulation

±1%

Transient Voltage Regulation

±4%

Phase Displacement with Balance Load

120°±1°

Phase Displacement with 100% Unbalance Load

120°±3°

Total Harmonic Distortion with linear load

<3%

Crest Factor

3:1

DC Characteristic

DC Bus Voltage

396V

DC Ripple

<1%

Environmental

Operating Temperature Range

0°C to 40°C

Relative Humidity

95% non condensing

Acoustic Noise

<50dBA

Physical

Dimensions (WxDxH) (mm)

550 x 950 x 1200mm

Weight without Batteries (kg)

250

270

280

290

300

400

450

Cooling

Forced Air

Other Products in 'UPS Systems' category
UPS System
UPS System
UPS System
UPS System
UPS System
UPS System
 
<< Back
 


  Contact Details  
NUTEK SYSTEM & CONTROL
323, 3rd Floor, Durga Tower, Raj Nagar Distt. Center, Ghaziabad - 201002, Uttar Pradesh, India
Phone:91-120-4380145/2825150
Fax:91-120-2825150
Send Mail     
Contact Now
Key Personnel
Mr. Mahendra Sharma (Director)
Mobile:+919411166636, +919810219151



Copyright © 2009 by NUTEK SYSTEM & CONTROL All Rights Reserved.