UPS System
Salient FeaturesTrue On - Line Pure Sinewave with Double Conversion TechnologyThis UPS offers you power you can trust all the time The double conversion technology is proven efficient reliable and provides Clean Computer Grade Power to critical Load. The load is completely protected against Spikes Surges Brownouts and Power failureHigh Frequency PWM InverterThe UPS can be interfaced with the host computer. In the event of extended mains failure the software will automatically save the current file and initiate an orderly shut down of the computer and the UPS system. Computer InterfaceThe UPS can be interfaced with the host computer. In the event of extended mains failure the software will automatically save the current file and initiate an orderly shut down of the computer and the UPS system.Auto RetransferThe UPS has a unique feature of transferring the load automatically back to inverter as long as inverter is healthy and the load is within the capacity of the UPSThe feature is very helpful for starting of loads which draw starting in - rush current more than capacity of the UPS. The UPS goes to bypass on sensing over load and comes back on inverter supply automatically once the load current is settled to normal level.Ergonomical ConstructionThe UPS is engineered for easy accessibility to facilities quick servicing resulting in low MTTR. The unit stands on Castor Wheels easy to install and operate with high degree of reliability.Options- Software for auto shutdown
- SNMP for remote monitoring
- Potential free contacts for remote indications and shutdown.
Conformance to International- Product Testing: IEC 146
- Safety: EN 50091 - 1
- EMI / RFI Suppression: EN50091 - 2
| Capacity(KVA / KW) | 3/2.4 | 5/4 | 6/4.2 | 8/6.4 | 10/7 | | Input | Voltage Range
| 160V to 275V
| Frequency
| 50 Hz ± 5%
| | Output | | Voltage | 220 / 230 V, 1 Phase
| | Frequency | 50 ± 0.05 Hz (Free running
| | Power Factor | 0.8 | 0.8 | 0.7 | 0.8 | 0.7 | | Overload | 125% for 10 min and 150 % for 1 min | | Steady State Voltage Regulation | ± 0.5% | | Transient Voltage Regulation | ±2% | Total Harmonic Distortion with linear load | <3% | | Crest Factor | 3:1 | | DC Characteristics | | DC Bus Voltage | 192V | | DC Ripple | <1% | | Environmental | | Operating Temperature Range | 0°C to 40°C | | Relative Humidity | 95 % non condensing | | Acoustic Noise | < 50dBA | | Physical | | Dimension (W x D x H) (mm) | 390 x 760 x 485 | 390 x 910 x 550 | | Weight without Batteries (Kg) | 150 | 150 | 150 | 210 | 210
|
Specification subject to change
|