Technical Specification
|
|
Input Rating
|
Power supply
|
3 Phase, 380V / 415V, 50 / 60 Hz
|
|
Allowable variations
|
Voltage: +10%, -15%, Frequency : +/-5%, imbalance less than 3%
|
|
Output voltage
|
3 phase, 380V to 440V (same as input voltage)
|
|
Output Rating
|
Output frequency
|
1 to 128Hz
|
|
Frequency stability
|
Digital setting : +/- 0.01% of Max. frequency
(-10 C to +50 c)
Analog setting : +/- 0.2% of Max. frequency
(at 25 C +/- 10C)
|
|
Overload capacity
|
150% for one minute
|
|
|
Control system
|
Space vector modulation with bus ripple compensation
|
|
Control Specification
|
Frequency control range
|
1 to 128Hz
|
|
Adjustable current limit
|
30 to 200 % of rated current
|
|
Maximum frequency
|
1 to 128Hz
|
|
Base frequency
|
40 / 50Hz
|
|
Carrier frequency
|
5.3Hz fixed
|
|
Frequency setting
|
Up /Down keys, potentiometer 1 kohm (0.5 W),Raise / Lower switch, Analog input : 0 to 10V, 0 to -10V, 4 to -20mA, +10V to -10V (polarity based speed reversal), 8 preset frequencies with x1, x2 & x3 terminals
|
|
Frequency resolution
|
Digital : 0.01Hz step (at Fmax. 50Hz) Analog : 0.05Hz step (at Fmax. 50Hz)
|
|
Jump frequency control
|
3 points with adjustable jump range
|
|
Accel / Decel. rate
|
0.1 to 128Hz per second (4 independently adjustable Accel. & Decel.)
|
|
Braking torque
|
Dynamic braking (20 to 150%)
|
|
Slip compensation
|
Available (Load current dependent)
|
|
Max./Min. frequency
|
Frequency lower limit / Frequency upper limit (Fstart to Fmax.)
|
|
Fault history display
|
Present fault and upto 19 previous faults
|
|
Starting frequency
|
1 to 10Hz
|
|
Inverter trip and error messages
|
Under voltage, Over voltage, Inverter Overload, Short circuit, CMOS error, Over current during acceleration / deceleration / steady state conditions, THR fault, Heat sink overheating & Electronic thermal overload trip.
|
|
Protection
|
Functions
|
Stall prevention, Auto restart during instantaneous power failure for 15ms duration
|
|
Analog output
|
Frequency / Motor Current
|
|
Indication and Control
|
External output
|
2Nos. Programmable open collector outputs, 1No. Fault alarm relay output and 1 no. Programmable relay output.
|
|
Display unit
|
4 Seven segment LED: Output frequency, RPM Load current & DC bus voltage 16 x 2 Character LCD with back-lit and 6 Keys touch pad for programming
|
|
Installation Location
|
Indoor not more than 1000 Mts. Above sea level. Do no install in a dirty location or expose to corrosive gases or direct sun rays.
|
|
Environmental Conditions
|
Ambient temperature
|
10 C to +40 C (-10 C to +50 C when mounted inside the switch board)
|
|
Humidity
|
90 % RH or less (non-condensing)
|
|
Cooling system
|
Forced air cooling type
|
|
Optional
|